Features of CKJ5 contactors: Vacuum contactors use vacuum interrupter as switching elements, the main circuit moveable and stationary contacts are sealed in the vacuum where the atmospheric pressure is lower than 1*10-2 Pa. Vacuum medium has good isolation and arc extinguishing ability, so the vacuum contactor is characterized as high isolation voltage, small contact stroke, low contact wear, long life and so on.
GL Type | Rated Current (A) | Rated Voltage (KV) | Rated Making Capacity (A) | Rated Breaking Capacity(A) | Limited Breaking Capacity(A) | Mechanical Life (Million times) | Electrical Life (Million times) | Hold Power (W) | Pick-up Power (W transient) | |
CKJ5-80/1.14 | 80 | 1.14 | 980 | 800 | 2000 | 1 | 6 | 295 | 10 | |
CKJ5-125/1.14 | 125 | 1.14 | 1500 | 1250 | 3000 | 1 | 6 | 345 | 21 | |
CKJ5-160/1.14 | 160 | 1.14 | 1600 | 1280 | 3000 | 1 | 6 | 345 | 21 | |
CKJ5-250/1.14 | 250 | 1.14 | 2500 | 2000 | 4500 | 1 | 6 | 500 | 30 | |
CKJ5-400/1.14 | 400 | 1.14 | 4000 | 3200 | 4500 | 1 | 6 | 860 | 28 | |
CKJ5-630/1.14 | 630 | 1.14 | 6300 | 5000 | 6000 | 1 | 6 | 1530 | 50 |