Features of permanent magnet vacuum Circuit breakers: This breaker adopts bistable permanent magnet mechanism, the integrated design of mechanical manual closing mechanism and mechanical manual opening mechanism. Permanent magnet mechanism opening is combined with spring opening, the distribution of opening speed is more ideal. Compared with spring operating breaker, movable units are less, significantly improving reliability and life, they are ideal replacement for spring operating breaker.
GL Type | Rated Current(A) | Rated Voltage(KV) | Rated Ultimate Breaking Capacity(A) | Closing Power(W Transient) | Opening Power(W Transient) | Undervoltage Power(W) | Mechanical Life(Million times) | Electrical Life(Million times) | Weight(KG) | |
ZN7-400/1.14 | 400 | 1.14 | 7.5(9) | 1152 | 31 | 5 | .02 | .3 | 18 | |
ZK1-630/1.14 | 630 | 1.14 | 12.5 | 2782 | 48 | 5 | .02 | .3 | 42.3 | |
ZK1-1000/1.14 | 1000 | 1.14 | 12.5 | 4250 | 48 | 5 | .02 | .3 | 46 |